| Information | 
  | 
  | 
  | 
  | 
| Installation | 
  | 
Outdoor | 
Outdoor | 
Outdoor | 
| Recommanded setting pressure | 
Pa | 
130 | 
130 | 
130 | 
| Max. airflow (75%) | 
m³/h | 
1.650 | 
2.475 | 
3.600 | 
| Sound pressure level at 3m distance (75%) – Lp, A | 
dB(A) | 
45 | 
47 | 
48 | 
| Sound power level from the suction side device (75%) – Lw, A | 
dB(A) | 
52 | 
56 | 
61 | 
| Sound power level from the pressure side device (75%) – Lw, A | 
dB(A) | 
– | 
  | 
– | 
| Required height for maintenance operations | 
mm | 
1.800 | 
2.100 | 
2.300 | 
| Connection to the main station | 
  | 
  | 
  | 
  | 
| Exhaust air – pipe connection (DN) | 
mm | 
ø 355 | 
ø 400 | 
ø 400 | 
| Exhaust air – connection options | 
  | 
1-2 connections left/right/front side 
Standard : 1 x frontal (bypass laterally) | 
1-2 connections left/right/front side 
Standard : 1 x frontal (bypass laterally) | 
1-2 connections left/right/front side 
Standard : 1 x frontal (bypass laterally) | 
| Integrated elastic connector for pipe | 
  | 
Included | 
Included | 
Included | 
| Brine – Pipe connection | 
mm | 
ø 22 (Cu) | 
ø 28 (Cu) | 
ø 28 (Cu) | 
| Brine – Max. Airflow (Recommendation) | 
m³/h | 
1 | 
2,4 | 
2,8 | 
| Brine – Permitted antifreeze | 
  | 
Ethylene glycol | 
Ethylene glycol | 
Ethylene glycol | 
| Brine – Internal pressure loss airflow | 
kPa | 
22 | 
35 | 
31 | 
| Condensate – Pipe connection | 
mm | 
ø 20 | 
ø 20 | 
ø 20 | 
| Brine/ Condensate – Connection options | 
  | 
Left or right | 
Left or right | 
Left or right | 
| Energetic data | 
  | 
  | 
  | 
  | 
Max. Recoverable exhaust heat – heating period 
(Brine flow 4 ° C) | 
MWh | 
18 | 
32 | 
45 | 
| Max. Power of the heat exchanger at flow rate at recommended settings (brine flow 4 ° C) | 
kW | 
5,8 | 
11,6 | 
15,4 | 
| Ventilation and acoustic features | 
  | 
  | 
  | 
  | 
| Max Airflow (100%) at 130Pa | 
m³/h | 
2.200 | 
3.300 | 
4.800 | 
| Soud pressure level – 3 meters distance at 100/50% | 
db(A) | 
54 / 40 | 
52 / 41 | 
54 / 43 | 
| Sound power level on suction side at 100/50% | 
dB(A) | 
55 / 49 | 
62 / 52 | 
65 / 56 | 
| Sound power level on the pressure side at 100/50% | 
db(A) | 
– | 
– | 
– | 
| Integrated pressure control | 
  | 
  | 
  | 
  | 
| Digital pressure display | 
  | 
Included | 
Included | 
Included | 
| Max. increase of pressure | 
Pa | 
300 | 
300 | 
300 | 
| Electrical data | 
  | 
  | 
  | 
  | 
| Fan – Drive technology | 
  | 
EC-Motor | 
EC-Motor | 
EC-Motor | 
| Repair switch | 
  | 
Included | 
Included | 
Included | 
| Supply voltage | 
V / Hz | 
230 / 50 | 
230 / 50 | 
230 / 50 | 
| Max current consumption | 
A | 
2 | 
2,4 | 
3,3 | 
| Power consumption fan device (75%) at 130 Pa | 
W | 
177 | 
226 | 
355 | 
| SFP fan (75%) | 
W/m³/h | 
0,107 | 
0,091 | 
0,099 | 
| Max. fan power consumption (Motor) | 
W | 
465 | 
530 | 
740 | 
| Index fan protection | 
IP | 
54 | 
54 | 
54 | 
| Fan’s motor protection | 
  | 
Internally | 
Internally | 
Internally | 
| Fault signal and heat pump release | 
  | 
Contact for groupe message, digital display on the device | 
Contact for groupe message, digital display on the device | 
Contact for groupe message, digital display on the device | 
| Max acceptable exhaust air temperature | 
°C | 
40 | 
40 | 
40 | 
| Housing properties | 
  | 
  | 
  | 
  | 
| Weight (unfilled unit) | 
kg | 
173 | 
205 | 
364 | 
| Material | 
  | 
Steel (galvanized), Aluminum | 
Steel (galvanized), Aluminum | 
Steel (galvanized), Aluminum | 
| Other components | 
  | 
  | 
  | 
  | 
| Filter protection class (including filter monitoring) | 
  | 
G4 | 
G4 | 
G4 | 
| Integrate condensate tray with siphon | 
  | 
Included | 
Included | 
Included | 
| Smoke detector and bypass for free outflow in case of fire | 
  | 
Included | 
Included | 
Included |